H971SP
- System Technology Exclusive Pulse Reset Technology™
- Amperage Range ±200 ADC
- Sensor Supply Voltage 12-24VDC*
- Supply Current 35mA max.**
- Insulation Class 600VDC
- Temperature Range -30° to 60°C (-22° to 140°F)
- Humidity Range 10-90% RH non-condensing
- Output Bi-polar 4-20mA (fixed span, specified by customer)
- Accuracy Below 100A ±0.5A (combined linearity, hysteresis, and repeatability)***
- Accuracy Above 100A ±0.5% full scale (combined linearity, hysteresis, and repeatability)***
- Withstand Current 25,000ADC
* For currents over 120A, supply voltage must be at least 15V.** At zero load current: 35mA max.; at 200mA load current: 55mA to 100mA depending on supply voltage and current polarity.*** For single conductor through product (no wraps).