- CURRENT MONITORING
- Current Switch
- Fixed Trip
- Adjustable Trip
- Adjustable Trip, N.C. Out
- Auto Calibration, LV Out
- Current Switch with Relay
- Fixed Trip
- Adjustable Trip
- Current Transducer
- 4-20mA Out
- 0-5VDC Out
- 0-10VDC Out
- Current Transducer with Relay
- 4-20mA Out
- 0-5VDC Out
- Field Mount
- Motor Control
- Status Relay
- AC Load Status
- Variable Frequency Sensor
- DC Current Transducer
H308 Split core, maximum current: 50A AC, adjustable trip point: 0.75A minimum, integral N.O. 1A@30VAC/DC output, LED status, induced powered, micro-sized housing. CE, UL, RoHS. |
|
H608 Split core, maximum current: 175A AC, adjustable trip point: 0.5, integral N.O. 1A@30VAC/DC output, LED status, induced powered, mini-sized housing. CE, UL, RoHS. |
|
H708 Solid core, maximum current: 135A AC, adjustable trip point: 1A or less, integral N.O. 1A@30VAC/DC output, LED status, induced powered. CE, UL. |
|
H808 Solid core, maximum current: 50A AC, adjustable trip point: 0.75A or less, integral N.O. 1A@30VAC/DC output, LED status, induced powered, mini-sized housing. CE, UL, RoHS. |
|
H908 Split core, maximum current: 135A AC, adjustable trip point: 2.5A or less, integral N.O. 1A@30VAC/DC output, LED status, induced powered. CE, UL. |
|
H609 Split core, maximum current: 50A AC, adjustable trip point: 1.25A or less, integral N.O. 0.2A@120VAC/DC output, LED status, induced powered, mini-sized housing. UL, RoHS. |
|
H701 Solid core, maximum current: 135A AC, adjustable trip point: 1A or less, integral N.O. 1A@30VAC/DC output, without LED status, induced powered. CE, UL. |
|
H709 Solid core, maximum current: 135A AC, adjustable trip point: 1A or less, integral N.O. 0.2A@120VAC/DC output, LED status, induced powered. UL. |
|
H709HV Solid core, maximum current: 135A AC, adjustable trip point: 1A or less, integral N.O. 1A@250VAC/DC output, without LED status, induced powered. CE. |
|
H809 Solid core, maximum current: 50A AC, adjustable trip point: 0.75A or less, integral N.O. 0.2A@120VAC/DC output, LED status, induced powered. UL. |
|
H909 Split core, maximum current: 135A AC, adjustable trip point: 2.5A or less, integral N.O. 0.2A@120VAC/DC output, LED status, induced powered, mini-sized housing. UL. |
|
H909HV Split core, maximum current: 135A AC, adjustable trip point: 2.5A or less, integral N.O. 1A@250VAC/DC output, without LED status, induced powered. CE. |