E8950

Downstream (device) Interfaces:

  • Physical Layer: 2-wire RS-485
  • Protocol: Modbus RTU
  • Baud Rate: 9600 to 38400 (selections vary with Modbus devices used)

Upstream (controller) Ethernet Interface:

  • Physical Layer: 10/100 Mb Ethernet
  • Protocol: BACnet IP

Upstream (controller) Serial Interface:

  • Physical Layer: 2-wire RS-485
  • Protocol: BACnet MS/TP
  • Baud Rate: 300-115, 200, with auto-detection

Input Power Requirements:

  • Supply Voltage: 9-30VDC or VAC or 5VDC
  • Nominal Current Draw @ 12V: 150mA

Environmental:

  • Operating Temperature: -40°C to 40°C (-40°F to 104°F)
  • Relative Humidity: 5-90% RH noncondensing