H663SM-24HE
- Operating Temp. Range: 0 to 60°C (32° to 140°F) (<95%RH, non-condensing)
- Storage Temp. Range: -40° to 70°C (-40° to 158°F)
- Power Source 120VAC (+10/-25%) line-to-neutral, 50/60Hz
Measured Current Inputs:
- Number of Channels: 42, 30, 24, 12, or 1 (Choose one option)
- Frequency: 50/60Hz
- Sample Rate: 1280Hz
- Update Rate: 1.2 sec
- Accuracy: ±5% of reading 5A to 50A
- Connection to Conductor Inductive Split-core CT?†
Network Communications:
- Type Modbus® RTU
- Connection DIP switch-selectable 2-wire or 4-wire
- Address DIP switch-selectable address 1 to 247
- Baud Rate DIP switch-selectable 2400, 4800, 9600, 19200
- Parity DIP switch-selectable NONE, ODD, EVEN
- Communication Format 8 data-bits, 1 start-bit, 1 stop-bit
- Termination 5-position pluggable connector (TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Defaults:
- Warning Register 60% of current sensor rating (configurable)
- Alarm Register 70% of current sensor rating (configurable)
- Current Settings 20 Amp
† Do not apply 300V Class current transformers to circuits having a line-to-neutral voltage greater than 300V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.