E31C42
Inputs:
- Input Power 90-277 VAC, 50/60 Hz
Accuracy:
- Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
- Voltage ±0.5% of reading 90-277 V line-to-neutral
Operation:
- Sampling Frequency 2560 Hz
- Update Rate 1.8 s
- Overload Capability 22 kAIC
Network Communications:
- Type Modbus® RTU
- Connection DIP switch-selectable 2-wire or 4-wire, RS-485
- Address DIP switch-selectable address 1 to 247 (pairs of 2)
- Baud Rate DIP switch-selectable 9600, 19200, 38400
- Parity DIP switch-selectable NONE, ODD, EVEN
- Communication Format 8 data-bits, 1 start-bit, 1 stop-bit
Environmental:
- Operating Temperature 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
- Storage Temperature -40° to 70°C (-40° to 158°F)
Safety:
- UL508, EN61010