Power/Energy Monitoring Banner

E30A084

Inputs:

  • Input Power 90-277 VAC, 50/60 Hz

Accuracy:

  • Power/Energy IEC 62053-21 Class 1, ANSI C12.1-2008
  • Voltage ±0.5% of reading 90-277 V line-to-neutral

Operation:

  • Sampling Frequency 2560 Hz
  • Update Rate 1.8 s
  • Overload Capability 22 kAIC

Network Communications:

  • Type Modbus® RTU
  • Connection DIP switch-selectable 2-wire or 4-wire, RS-485
  • Address DIP switch-selectable address 1 to 247 (pairs of 2)
  • Baud Rate DIP switch-selectable 9600, 19200, 38400
  • Parity DIP switch-selectable NONE, ODD, EVEN
  • Communication Format 8 data-bits, 1 start-bit, 1 stop-bit

Mechanical:

  • Ribbon Cable Support 4 ea 4 ft. (0.9 m) flat ribbon cables ship standard; up to 20 ft. (6 m) available

Environmental:

  • Operating Temperature 0° to 60°C (32° to 140°F) (<95% RH noncondensing)
  • Storage Temperature -40° to 70°C (-40° to 158°F)

Safety:

  • UL508, EN61010