H8238E
- Voltage Tolerance 90 - 132VAC line-to-neutral
- Electrical Services 120/240 VAC with neutral, 208Y/120 VAC line to neutral
- Power Consumption 50VA
- Insulation Class 600VAC†
- Internal Isolation 2500VAC
- LCD Display 1.2" (31mm) x 3.8" (97mm) viewing area, 160 segments, back-lit with green LEDs
- Sample Rate 1280Hz
- Operating Temp. Range 0° to 50°C (32° to 122°F) (<95%RH, non-condensing)
- Storage Temp. Range -40° to 70°C (-40° to 158°F)
- Systems Accuracy ±1% of reading from 2% to 100% of the rated current of the CTs, accomplished by matching the CTs with a meter and calibrating them as a system
- Frequency 50/60Hz
- Protection Class NEMA 1
*not supported at >1600A**not supported at >2400A† Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings. Note: Meter and CT serial numbers must match.