E34E08
Voltage Inputs
- Measurement Voltage: 90 to 300 Vac line-to-neutral, 50/60 Hz
- Control Power: 100 to 277 Vac line-to-neutral, 50/60 Hz, 15VA
Accuracy
- Power/Energy: IEC 62053-21 Class 0.5, ANSI C12.20 class 0.5
- Voltage: ±0.5% of reading 90 to 277 V line-to-neutral
- Current: ±0.5% of reading from 2% to 100% full scale
Operation
- Sampling Frequency: 2560 Hz
- Update Rate: 2 seconds (both panels)
- Overload Capability: 22 kAIC
Serial Communication
- Physical Interface: 2-wire RS-485
- Protocols Supported: Modbus RTU or BACnet MSTP
- Address Range: 1 to 247 for Modbus RTU; 0-127 for BACnet MS/TP
- Baud Rate: 9600, 19200, 38400
- Parity: Modbus RTU: NONE, ODD, EVEN BACnet MS/TP: NONE (fixed)
Ethernet Communication
- Physical Interface: Rj45 connector with 10/100 Mbit Ethernet
- Protocols Supported: Modbus TCP, BACnet IP, SNMP V2c
Terminal Block Torque
- Removable Connectors: 4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
Operating Conditions
- Operating Temp Range: 0 to 60°C (32 to 140°F) (<95% RH non-condensing)
- Storage Temp Range: -40 to 70°C (-40 to 158°F)
- Altitude of Operation: 3000 m
- Mounting Location: Indoor use, dry location
Warranty
- Limited Warranty: 5 years
Compliance Information
- Agency Approvals: IEC/EN61010-1
- Installation Category: Cat III, pollution degree 2