U001-0002

  • Temperature Rating 105°C (221°F) continuous
  • Pressure Rating At 38°C (100°F) 228BR: 200psi; 220SS: 400psi; At 105°C (221°F) 228BR: 165psi; 220SS: 325psi
  • Recommended Design Flow Range 0.5 to 30 ft/sec (0.15 to 9 m/sec); initial detection below 0.3ft/sec
  • Wetted Materials UHMW-PE bearing, polyamide impeller, tungsten carbide shaft, EPDM O-rings
  • Accuracy 1% F.S. over recommended design flow range; ±4% of reading within calibration range*
  • Repeatability ±0.3% of full scale over recommended design flow range*
  • Linearity ±0.2% of full scale over recommended design flow range*
  • Transducer Excitation Quiescent current 600uA@8VDC to 35VDC max.; Quiescent voltage (Vh)=Vsupply - (600mA*Zsupply); On-State (Vlow) Max 1.2VDC@40mA current limit (15 O overall+0.7VDC)
  • Output Frequency 3.2Hz to 200 Hz
  • Output Pulse Width 5 msec ±25%

* =10 upstream and =5 downstream straight pipe diameters, uninterrupted flow.