U001-0096
- Wetted Materials (Sensor stem, mounting adapter, isolation valve, and nipple) 316 Stainless steel
- Sensor Tip GF polyphenylene sulfide (PPS)
- Operating temperature Electronics: 150°F (65°C); LCD: 150°F (65°C)
- Power required for analog output versions: 8-35 VDC, 30mA max.
Maximum Pressure Rating:
- 1000 psi (68.9 bar) @ 70°F (21°C)*
- 900 psi (62 bar) @ 100°F (37.8°C)*
- 670 psi (46.1 bar) @ 140°F (60°C)*
- 225 psi (15.5 bar) @ 180°F (82°C)*
- Recommended Design Flow Range 1 to 20 ft/sec
- Extended flow range < 0.3 to 20 fps
- Pressure Drop 0.5 psi or less @ 10 ft/sec for all pipe sizes 1.5" dia and up.
- Accuracy To +/- 1% of rate over optimum flow range; Custom wet calibration: On request
- Straight Pipe Requirement install sensor in straight pipe section with a minimum distance of 10 diameters upstream and 5 diameters downstream to any bend, transition, or obstruction.
- Repeatability +/- 0.5%
- Enclosure Polypropylene with Viton® sealed acrylic cover. Meets NEMA 4X specifications
- Wire Connections Removable headers with screw type terminals within the electronics housing, ½” conduit thread connection.
- Programming Data Industrial A-301 connector cable and SDI Series software
- Accessories ASDI Programming Kit, A1027 Hot Tap Adapter Nipple
* Non-Shock