H8163-0100-0-3

  • Voltage Tolerance 90 - 300VAC line-to-neutral
  • Electrical Services Any service where the phase A-N voltage is =300VAC & the phase-to-phase voltage is < 480VAC nom, with neutral
  • Power Consumption 50VA
  • Insolation Class 600VAC†
  • Internal Isolation 2500VAC
  • LCD Display 1.2" (31mm) x 3.8" (97mm) viewing area, 160 segments, back-lit with green LEDs
  • Sample Rate 1280Hz
  • Operating Temperature Range 0° to 50°C (32°F to 122°F) (<95%RH, non-condensing)
  • Storage Temperature Range -40° to 70°C (-40°F to 158°F)
  • Systems Accuracy ±1% of reading from 2% to 100% of the rated current of the CTs...accomplished by matching the CTs with a meter and calibrating them as a system
  • Frequency 50/60Hz
  • Pulse Output N.O., Opto-FET, 100mA @ 24VAC/DC
  • Pulse Rate 0.10*, 0.25**, 0.50, or 1.00 kWh per pulse
  • Pulse Width 200msec closed
  • Phase Loss Alarm Output N.C., Opto-FET, 100mA @ 24VAC/DC; Fixed threshold 25% below any other phase. Always open as long as alarm persists
  • Protection Class NEMA 1

*not supported at >1600A**not supported at >2400A†Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings. Note: Meter and CT serial numbers must match.