Sensaphone Express II



Sensaphone Express II

Specifications


Name: Sensaphone Express II
Product #: FGD-6700
Monitoring Capacity: 8 universal input channels standard configurable as:
Normally open dry contact
Normally closed dry contact
Pulse counter
4-20mA analog with custom look up table
0-5 Volt analog with custom look up table
Built-in power failure monitoring
Built-in sound level monitoring (smoke or fire alarm)
Output Type: 1 built-in relay, SPST latching 2A 250 VAC
Expansion: 32 additional channels available for input/output expansion
Programming: All parameters can be programmed from the local keypad or any remote touch-tone phone
Message Length: User selectable 5, 7 or 11 seconds per input channel
Message Types: 1 recorded ID message
1 recorded alarm message for each input channel
Telephone Numbers: Total of 48 phone numbers with 32 digits each
Allows alarm specific dialing
Multiple phone lists for day/night/weekend
Dialing Format: Touch-tone, pulse, or auto-detect
Phone Connector: RJ11C
Activity Log: Built in RS232 port
Can automatically print alarm activity to a local printer
Local Indications: Built in LCD display to show alarm dialing status
Dual-color LED indication for each input channel
Power Requirements: 110VAC/220VAC
Internal Battery Backup: 12 hour Gel Cell with built-in charger
Operating Temperatures: 32-120°F
Operating Humidity: 0-90%, non-condensing
Storage Temperatures: 0-130°F
Dimensions: 14.4″ x 12.4″ x 7.3″
Weight: 15 lbs.
Enclosure: NEMA-4 fiberglass with latched window cover