- PRESSURE
- Differential
- Dry Media
- Wet Media
- Electropneumatic
- Analog Input
- Analog/Dry Contact
- Gauge
- Standard
- Economy
- Specialty Gauge
- Digitally Controlled
- Display Pressure/Vacuum
PXPLX01S
- Media Compatibility Dry air or inert gas
- Input Power: 12-30VDC, or 24VAC nominal
- Output Field-selectable: 2-wire, loop-powered 4-20mA (DC only, clipped and capped) or 3-wire 0-5V/0-10V
- Pressure Ranges: Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S. (25 pa/50 pa/100 pa/250 pa, F.S.), switch selectable; Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S. (±25 pa/±50 pa/±100 pa/±250 pa, F.S.), switch selectable
- Response Time Standard: T95 in 20 sec, Fast: T95 in 2 sec, switch selectable Mode Unidirectional or bidirectional, switch selectable
- Mode Unidirectional or bidirectional, switch selectable
- Display (option) Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
- Proof Pressure 3 psid (20.6kPa)
- Burst Pressure 5 psid (34.5kPa)
- Accuracy ±1% F.S. of selected range (combined linearity and hysteresis)
- Temperature Effect 1" 0.05%/°C; 10"
- Zero Drift (1-year) 1" 2.0% max.
- Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
- Operating Environment 0°- 60°C (32° to 140°F); 0 to 90% RH non-condensing
- Fittings Brass barb; 0.24” (6.1mm) o.d.
- Physical UL 94 V-O Fire Retardant ABS
EMC Conformance: EN 61000-6-3:2001 Class B, EN 61000-6-1:2001, EN 61000-3-2:2000, EN 61000-3-3:2001, EMC Test Methods: CISPR 22:1997 (Amended A1:2000, Class B A2:2002), IEC 61000-4-2:2002, IEC 61000-4-3:2006, IEC 61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC 61000-4-11:2004.EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).