U010-0071
- Thermostat Power Requirements 19-30 VAC 50 or 60 Hz; 2 VA Class 2
- Operating Conditions 0° to 50°C (32° to 122°F); 0% to 95% R.H. non-condensing
- Storage Conditions -30° to 50°C (-22° to 122°F); 0% to 95% R.H. non-condensing
- Temperature Sensor Local 10 K NTC thermistor
- Resolution Temp: ± 0.1°C (± 0.2°F)
- Control Accuracy Temp: ±0.5°C (±0.9°F ) @ 21°C (70°F) typical, calibrated
- Occupied and Unoccupied Setpoint Range Cooling 12.0° to 37.5°C (54° to 100°F)
- Occupied and Unoccupied Setpoint Range Heating 4.5° to 32°C (40° to 90°F)
- Room and Outdoor Air Temperature Display -40° to 50°C (-40° to 122°F)
- Proportional Band for Room Temperature Range Control Cooling & Heating: 1.8°C (3.2°F )
- Binary Inputs Dry contact across terminal BI1, BI2 & UI3 to Scom
- Outputs Rating Triac output: 30 VAC, 1 Amp max., 3 Amp in-rush; Analog: 0 to 10 VDC into 2k? resistance min.
- Economizer Analog Output Rating 0 to 10 VDC into 2k? resistance min.
- Economizer Analog Output Accuracy ±3% typical
- Wire Gauge 18 gauge maximum, 22 gauge recommended
- Dimensions 4.94” x 3.38” x 1.13”
- Approximate Shipping Weight 0.75 lb (0.34 kg)
Agency Approvals:
- UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN; XAPX (US) and XAPX7 (Canada)
- FCC Compliant to CFR 47, Part 15, Subpart B, Class A (US)
- Industry Canada ICES-003 (Canada)
- CE EMC Directive 89/336/EEC (Europe Union)
- C-Tick AS/NZS CISPR 22 Compliant (Australia / New Zealand); Supplier Code Number N10696