- PRESSURE
- Differential
- Dry Media
- Wet Media
- Electropneumatic
- Analog Input
- Analog/Dry Contact
- Gauge
- Standard
- Economy
- Specialty Gauge
- Digitally Controlled
- Display Pressure/Vacuum
PWXX04C
- Input Power: 12-30VDC, or 24VAC nominal
- Maximum Current Draw DC: 125mA; AC: 280mA
- Output 3-wire transmitter; user selectable 4-20mA, (clipped and capped)/0-5V/0-10V†
- Accuracy @ 25°C* Range A, B, C: ±1% F.S.; Range D: ±2% F.S.**
- Surge Damping Electronic; 5-second averaging
- Test Mode Overrides output to full-scale (20mA, 5V, 10V)
- Pressure Ranges: (Selectable) 0-10/20/50/100psid (0-0.34/0.69/1.72/3.45 bar)
- Product Operating Environment -10° to 55°C (-140° to 130°F); 0 to 90%RH, non-condensing
- Long Term Stability ±0.25% per year
- Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
- Status Indication Dual-color LED: Green = Normal, Green Blinking = Low > High, Red = Overrange, Red Blinking = Overpressure
- Housing Material White powder-coated aluminum
Sensor:
- Media Compatibility Media compatible with 17-4 PH stainless steel
- Proof Pressure Max. 2x F.S. range
- Burst Pressure Max. 5x F.S. range
- Temperature Compensated Range 0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor, TC Span<±1.5% of product F.S. per sensor, (2 sensors per unit)
- Media Temperature Limits -20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing
- Fittings 1/8" NPT female thread, 17-4 PH stainless
†Minimum input voltage for 4-20mA operation: 250 ohm loop (1-5V) = 12 VDC; 500 ohm loop (2-10V) = 15 VDC; Minimum input voltage for volt operation: 0-5VDC output = 12 VDC; 0-10VDC output = 15 VDC. *Accuracy combines linearity, hysteresis, and repeatability.**FS is defined as full span of selected range in bi-directional mode.