Pressure Banner

PWLN05S

  • Input Power: 12-30VDC/24VAC nominal
  • Maximum Current Draw DC: 125mA; AC: 280mA
  • Output 3-wire transmitter; user selectable 4-20mA, (clipped and capped)/0-5V/0-10V†
  • Accuracy @ 25°C* Range A, B, C: ±1% F.S.; Range D: ±2% F.S.**
  • Surge Damping Electronic; 5-second averaging
  • Test Mode Overrides output to full-scale (20mA, 5V, 10V)
  • Pressure Ranges: (Selectable) 0-10/20/50/100psid (0-0.34/0.69/1.72/3.45 bar)
  • Product Operating Environment -10° to 55°C (-140° to 130°F); 0 to 90%RH, non-condensing
  • Long Term Stability ±0.25% per year
  • Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
  • Status Indication Dual-color LED: Green = Normal, Green Blinking = Low > High, Red = Overrange, Red Blinking = Overpressure
  • Housing Material White powder-coated aluminum

Sensor:

  • Media Compatibility Media compatible with 17-4 PH stainless steel
  • Proof Pressure Max. 2x F.S. range
  • Burst Pressure Max. 5x F.S. range
  • Temperature Compensated Range 0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor, TC Span<±1.5% of product F.S. per sensor, (2 sensors per unit)
  • Media Temperature Limits -20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing
  • Fittings 1/8" NPT female thread, 17-4 PH stainless

†Minimum input voltage for 4-20mA operation: 250 ohm loop (1-5V) = 12 VDC; 500 ohm loop (2-10V) = 15 VDC; Minimum input voltage for volt operation: 0-5VDC output = 12 VDC; 0-10VDC output = 15 VDC. *Accuracy combines linearity, hysteresis, and repeatability.**FS is defined as full span of selected range in bi-directional mode.