- PRESSURE
- Differential
- Dry Media
- Wet Media
- Electropneumatic
- Analog Input
- Analog/Dry Contact
- Gauge
- Standard
- Economy
- Specialty Gauge
- Digitally Controlled
- Display Pressure/Vacuum
PVE04AM
Electrical:
- Supply Voltage: 10-28VDC
- Output: 1-5VDC (3 wire) or 4-20mA (2-wire)
- Load Impedance >100kO
- Standard Connection Cable gland 24” (600mm) length
- Pressure Port 1/4”NPT Male
Performance at 25°C (77°F):
- Accuracy *: ±0.25% BFSL **
- Media Compatibility (PG/PV) Fluids & gases compatible with 17-4 stainless steel
- Pressure Cycles >100 million cycles
- Over Pressure 2x F.S. without change in calibration
- Burst Pressure 5x rated pressure or 20,000 PSI
Environmental:
- Operating Temp. Range -40° to 85°C (-40° to 185°F)
- Compensated Temp. Range 0° to 55°C (32° to 130°F)
- Total Error Band Over Temp. <±1% of FS
- Humidity 0-95% RH, non-condensing
* Accuracy includes nonlinearity and hysteresis.** BFSL = Best fit straight line