Leak Detection Banner

U006-0062

SPECIFICATIONS (LD300 Control Panel)

  • Input Power: 5VDC ±10%
  • Maximum Cable Length 300 ft. (91 m)
  • Detection Response Time < 20 sec. (10 sec. typical)
  • Relay Output 2 Form C relays (leak and fault); 1A@24VDC, 0.5A resistive@120VAC

Operating Environment:

  • Temperature: 0° to 50°C (32° to 122°F)
  • Humidity 5% to 95% RH, non-condensing
  • Altitude 15,000 ft. (4,572m) max
  • Storage Environment -20° to 70°C (-4° to 158°F)
  • Weight 3 oz. (85 g)

SPECIFICATIONS (Cables)

  • Plenum Rating SC: CL2P/CMP C(UL); NSC: CL3P/CMP C(UL) California State Fire Marshall approved
  • Shear Strength SC/NSC: >180 lbs (>81.65 kg); SC-C: 160 lb (72.6 kg)
  • Cut Through Resistance SC/NSC: >40 lbs (>18.2 kg) with 0.005” (0.13 mm) blade; SC-C: >50 lbs (>27.7 kg) with 0.005” (0.13 mm) blade
  • Abrasion Resistance SC/NSC: 60 cycles per UL 719; SC-C: >65 cycles per UL719
  • Connector SC/NSC: 4 pin, 1” (25.4 mm) diameter, circular, locking, 4 pin; SC-C: 0.5” (13 mm) diameter

Operating Environment:

  • Temperature SC/NSC: 0° to 75°C (32° to 167°F); SC-C: 90°C (194°F) max.; SC-H: -20° to 90°C (-4° to 140°F)
  • Humidity SC/NSC: 5% to 95% RH non-condensing
  • Altitude SC/NSC: 10,000 ft. (3,048 m) max.
  • Storage Environment SC: -30° to 85°C (-22° to 185°F); NSC: 0° to 75°C (32° to 167°F)
  • Agency Approvals:LD300: CE; RoHS compliant SC: CE; UL E162948; RoHS compliant NSC: UL E118871; UL 13, power limited circuit cable; UL 444, communication cables; NFPA 262; plenum flame test (UL 910); NEC Articles 725 and 800; RoHS compliant