U007-0009
- Humidistat Power Requirements 19-30 VAC 50 or 60 Hz; 2 VA (RC & C) Class 2
- Operating Conditions 0° to 50°C (32° to 122°F); 0% to 95% R.H. non-condensing
- Storage Conditions -30° to 50°C (-22° to 122°F); 0% to 95% R.H. non-condensing
- Resolution Temp: ± 0.1°C (± 0.2°F); Humidity: ± 0.1%
- Control Accuracy Humidity: ±3% RH from 20 to 70% RH at 21°C (70°F)
- Humidification Setpoint Range 10% RH to 90% RH
- Dehumidification Setpoint Range 15% RH to 95% RH
- Outdoor Air Temperature Range -40° to 50°C (-40° to 122°F)
- Binary Inputs Relay dry contact only across Scom and DI1 terminals
- Contact Output Rating Each relay output: 30VAC, 1A max.; 30VAC, 3A in-rush
- Analog Output Rating 0-10VDC into 2kO resistance min.
- Wire Gauge 18 gauge maximum, 22 gauge recommended
- Dimensions 4.94” x 3.38” x 1.13”
- Approximate Shipping Weight 0.75 lb (0.34 kg)
Agency Approvals:
- UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN; XAPX (US) and XAPX7 (Canada)
- FCC Compliant to CFR 47, Part 15, Subpart B, Class A (US)
- Industry Canada ICES-003 (Canada)
- CE EMC Directive 89/336/EEC (Europe Union); C-Tick AS/NZS CISPR 22 Compliant (Australia / New Zealand); Supplier Code Number N10696