- PRESSURE
- Differential
- Dry Media
- Wet Media
- Electropneumatic
- Analog Input
- Analog/Dry Contact
- Gauge
- Standard
- Economy
- Specialty Gauge
- Digitally Controlled
- Display Pressure/Vacuum
EP2100S3
- Input Power: 24VAC/DC nominal,30VAC max.; 150mA max.
- Control Input 4-20mA/0-5V/0-10VDC; jumper-selectable
- Input Impedance 4-20mA, 250 ohm; 0-5V/0-10VDC, 10k ohm
- Manual Override Jumper-selectable mode, digital pushbutton adjust
- Accuracy 1% FS; combined linearity, hysteresis, repeatability
- Compensated Temperature Range -4° to 65°C (25° to 140°F)
- Temperature Coefficient ±0.05%/°C
- Operating Environment 10-90% RH, non-condensing
- Air Capacity 523 in3/min@45 psi (8570cm3/min@310.3 kPa); 333 in3/min@20 psi (5456cm3/min@137.9 kPa)
- Supply Pressure 45 psig max.
- Control Range 0-20 psig or 3-15 psig, jumper-selectable
- Pressure Differential 0.1psig (supply to branch)
- Pressure Indication Electronic, 3-1/2 digit LCD
- Minimum Tubing Length 15 feet*
- Port Connection 1/8” i.d. poly tubing
- Media Connection Clean, dry air, or inert gas. Do not use with oxygen service
*For shorter tubing runs use AA45 Pneumatic CapacitorEMC Conformance: EN 61000-6-3:2001 Class B, EN 55022 Class B, EN 61000-6-1:2001EMC Test Methods: CISPR 22:2005, Class B, IEC 61000-4-2:2001, IEC 61000-4-3:1998; IEC 61000-4-4:1995, IEC 61000-4-5:1995, IEC 61000-4-6:1997, IEC 61000-4-8:2001EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).