EP3030S2
- Input Power: 22-30VDC 20-30VAC, 47-63 Hz.,150mA max. average, 350mA peak
- Control Input 4-20mA/0-5V/0-10VDC; switch-selectable, Tri-State, PWM
- Input Impedance 4-20mA, 250 ohm; 0-5V/0-10VDC, 10k ohm
- Manual Override Digital pushbutton adjust, switch-selectable mode
- Accuracy 1% FS; combined linearity, hysteresis, repeatability @20°C (68°F) ambient
- Temperature Coefficient ±0.1%/°C
- Operating Environment 10-90% RH, non-condensing -4°C to 60°C
- SCIM 523 in3 /min @45psi; (8570 cm3 /min @ 310.3kPa); 333 in3/min @ 20psi (5457 cm 3/min @ 137.9 KPa)
- Supply Pressure Min: (0.1psi + user F.S. pressure); Max: 45psig
- Control Range User programable Zero selectable from 0-25psi: Full scale 0-25psi
- Pressure Differential 0.1psig (supply to branch)
- Pressure Indication Electronic, 3-1/2 digit backlit LCD
- Minimum Tubing Length 15 feet*
- Port Connection 1/8” i.d. poly tubing
- Media Connection Clean, dry air, or inert gas. Do not use with oxygen service
*For shorter tubing runs use AA45 Pneumatic CapacitorEMC Conformance: EN 61000-6-3:2001 Class B, EN 55022 Class B, EN 61000-6-1:2001EMC Test Methods: CISPR 22:2005, Class B, IEC 61000-4-2:2001, IEC 61000-4-3:1998; IEC 61000-4-4:1995, IEC 61000-4-5:1995, IEC 61000-4-6:1997, IEC 61000-4-8:2001EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).