HT2XAS0D
- Input Power 15 to 30VDC/24VAC, 100mA max.
- Outputs, Analog Switch-selectable: 4-20mA or 0-10V/0-5VDC (switch affects both outputs)
- Outputs, Relay 2 Form C (SPDT), 1A 30VDC, resistive, 30W max.
- RH Sensor Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138
- Accuracy at 25°C from 10-80% RH* ±2%
- Reset Rate** 24 hours
- Stability ±1% @ 20°C (68°F) annually, for two years
- Hysteresis RH: 1.5% (typical), Temp: 1° to 10°F in 1°F increments
- Linearity Included in accuracy spec.
- Operating Humidity Range 0-100% RH (non-condensing)
- Temperature Coefficient ±±0.1%RH/°C above or below 25°C (typical)
- Operating Temperature Range 10°-35°C (50°-95°F)
- Temperature Accuracy ± 1.0°C ( ±1.8°F)
- Scaling RH: 0-100% RH; Temp: 10°-35°C (50°-95°F) or 0°-50°C (32°-122°F) menu selectable
- Calibration Offset RH: Adjustable ±10% in 0.1% increments; Temp: Adjustable ±10° in 0.1° increments
- Setpoint Range RH: 10-80% RH in 1% increments; Temp: Minimum to Full Scale in 1°F increments
* Specified accuracy with 24VDC supplied power with rising humidity**Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hoursOne side of transformer secondary is connected to signal common, so an isolation transformer or dedicated power supply may be required.