- AIR QUALITY
- Duct CO2 Sensors
- Deluxe
- Standard
- Wall CO2 Sensors
- Deluxe
- Standard
- Remote Mount
- Dual Analog Outputs
- CO & NO2 Sensors
- Duct CO Sensors
- Wall CO Sensors
- Wall CO &NO2 Sensors
- CO Monitoring Station
CWVS3XX5
- Input Voltage 20 to 30VDC, 24VAC
- Analog Output #1 4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)
- Analog Output #2 4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)
- Sensor Current Draw 200mA Maximum
- Operating Temperature Range 0° to 50°C (32° to 122°F)
- Housing Material High impact ABS plastic
CO2 Transmitter:
- Sensor Type Non-dispersive infrared (NDIR), diffusion sampling
- Measurement Range 0-2000 ppm
- Accuracy ±40 ppm ±8.5% of measured value
- Repeatability ±30 ppm ±4.5% of measured value
- Response Time <60 seconds for 90% step change
Relay Contacts:
- Electromechanical 1A@30VDC, resistive; 30W max.
NOTE: EMC Conformance: EN 61000-6-3:2001 (Amended by A11:2004) Class B, EN 61000-6-1:2001 EMC Test Methods: CISPR 22:2006 Class B, IEC 61000-4-2:2001, IEC 61000-4-3:2006, IEC 61000-4-4:2004, IEC 61000-4-6:2006, IEC 61000-4-8:2001.EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements).